DATA SHEET |
|
|
Rated Power |
5000 VA / 5000 W |
6000 VA / 6000 W |
Parallel Capability |
Up to 9 units |
GRID INPUT |
Voltage |
230 VAC |
Voltage Range |
110 - 280 VAC |
Frequency Range |
50 Hz / 60 Hz (Auto sensing) ± 4 Hz |
Power Factor |
≥ 0.98 @ Nominal Voltage (100% Load) |
THDi |
≤ 10% |
LOAD OUTPUT |
AC Voltage Regulation (Line&Batt. Mode) |
230 VAC ± 5% |
Frequency Range (Synchronized Range) |
46 ~ 54 Hz or 56 ~ 64 Hz |
Frequency Range (Batt. Mode) |
50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Harmonic Distortion |
≤ 3% THD (Linear Load); ≤ 5% THD (Non-linear Load) |
Transfer Time |
AC Mode to Batt. Mode |
0 ms |
Inverter to Bypass |
4 ms (Typical) |
Waveform |
Pure sine wave |
No Load Consumption |
40 W |
75 W |
|
EFFICIENCY |
Line Mode |
94% |
ECO Mode |
98% |
Battery Mode |
92% |
BATTERY |
Battery Voltage |
40 ~ 66 VDC |
Floating Charge Voltage |
54 VDC |
Overcharge Protection |
66 VDC |
SOLAR INPUT |
Solar Charger Type |
MPPT |
Maximum PV Array Power |
6000 W |
MPPT Range @ Operating Voltage |
120 ~ 430 VDC |
Maximum PV Array Open Circuit Voltage |
500 VDC |
Maximum Solar Charge Current |
100 A |
120 A |
Maximum AC Charge Current |
100 A |
120 A |
PHYSICAL |
Dimension, (D x W x H) |
140 x 295 x 468 mm |
Net Weight |
12 kg |
Communication Interface |
RS232, USB, DRY CONTACT, Wi-Fi, RS485 |
ENVIRONMENT |
Humidity |
5% to 95% Relative Humidity (Non-condensing) |
Operating Temperature |
-10°C to 50°C |
Storage Temperature |
-15°C to 60°C |
IP Degree of Protection |
IP21 |
|